Voltage dips and short power cuts: what they do to machines

Machines stop, drives show undervoltage, the PLC needs a reset, yet nobody lost power. How voltage dips, flicker and micro-cuts hit production, how to measure them and how to ride through.

Voltage dips and short power cuts: what they do to machines

A voltage dip or a micro-cut lasts a fraction of a second. That is long enough to reset a PLC, trip a frequency drive or drop a contactor. First find out whether the dips come from the grid or from your own machines, by measuring. Then protect the controls, and where a stop is costly, the whole line. Our guide to the right emergency power supply for your business compares UPS, generator and battery for longer cuts. Business battery systems that feed your critical loads keep them running through a dip, because the loads never see it.

The lights blink for a moment. Nobody lost power, the neighbours did not notice a thing. But the press shows an alarm, the drive on the conveyor says "undervoltage" and the PLC wants a reset. Twenty minutes later the line runs again, next to a crate of scrap.

What makes it expensive is that nobody counts these stops. The grid operator registers no outage. The generator never starts, because the voltage is back before it would. The small UPS under the office PC keeps the PC alive, but not the drive in the hall. IT managers on forums describe UPS units that switch off "when the power flickers" instead of switching to battery. So the stops come back, every storm, every few weeks, and each one costs a restart, a batch or a delivery.

A site in Gingelom had the same kind of problem with its solar panels: they regularly dropped out. Our system of 30 kVA with 46.2 kWh of battery put an end to that. The grid is now only a back-up when energy runs short. At a hunting lodge in the woods at Gedinne, only 180 V was left of the 3x230 V grid. Our system turns that into a stable 3x400 V and uses the weak grid only to charge the battery.

What is a voltage dip, and how is it different from a power cut?

A voltage dip is a sudden drop to between 90% and 1% of the normal voltage, for 10 milliseconds up to one minute. That is the definition of the European standard EN 50160, as quoted by Janitza and HyTEPS. Below 1% it counts as an interruption: the power is simply gone.

Event What happens to the voltage How long What you notice
Normal variationStays within 230 V plus or minus 10% (207 to 253 V)ContinuousNothing
Voltage dipFalls to between 90% and 1% of normal10 ms to 1 minute, usually under 1 secondLights blink; machines, drives or PCs may stop
Short interruption (micro-cut)Disappears completelyA fraction of a second to secondsEverything without back-up stops; clocks reset
Power cutDisappears completelyMinutes to hoursEverything stops
FlickerVaries quickly and repeatedlyUnder 1 second per variation, for as long as the load keeps switchingLights flicker; tiring for people
OvervoltageStays too highMinutes to hoursSolar inverters switch off

Too high a voltage is a different problem, with its own procedure at the grid operator. Our article on why a solar inverter trips on high grid voltage covers it. A voltage that is structurally too low on a small connection is explained in our article on a 3x230 V connection that is too weak.

What causes voltage dips and short power interruptions?

Most voltage dips start with a short circuit somewhere on the grid, and the rest with large loads switching on inside your own site. Janitza puts about 75% of dips in the medium-voltage grid: digging work, ageing cables, storms and animals on overhead lines. HyTEPS adds weather and switching by the grid operator.

Short interruptions often come from the grid protecting itself. ORES explains it plainly: micro-cuts usually result from an incident on the grid, which puts itself in safety and switches back on automatically. For you, that is a gap of a fraction of a second to a few seconds. For a drive or a PLC, it is a full stop.

The inside causes are yours to fix. HyTEPS notes that a motor can draw up to 10 times its rated current when it starts. That current pulls the voltage down on your own installation. Starting a transformer and faults inside your own site have the same effect. Our article on how a battery inverter carries the start-up current of a heavy machine explains the physics.

Tip

Note the time of every unexplained stop. If the stops line up with storms or with problems at the neighbours, look at the grid. If they line up with one machine starting, look inside.

Why does a short voltage dip stop your machines?

Because modern controls react within milliseconds, while the voltage only has to be gone for a moment to confuse them. HyTEPS and Janitza both name the same weak spots: PLCs, frequency drives, machine controls, servers and PCs.

Equipment What a dip does to it What it costs you
Contactor (the switch that holds a motor on)Loses its holding power and opensThe motor stops and does not restart on its own
PLC (the computer that runs the machine)Resets or gets confusedThe line needs a reset and a check before it restarts
Frequency drive (a controller that lets a motor start and run gently)Switches off with an undervoltage faultConveyor, pump or fan stops mid-process
PC, server, network switchRestarts or loses the connectionLost orders, a machine without instructions
Solar inverterDisconnects when the voltage leaves its limits (Synergrid C10/11)Solar production stops for a while

The dip itself lasts less than a second. The real cost is the restart. Think of an injection moulding press, a packaging line or a batch process. A machine that stops halfway through a cycle often leaves parts or a batch to scrap. Then someone has to find the fault, reset and check before the line runs again.

Those are sector figures from Janitza, not a promise for your site. For a small workshop, a stop is mostly lost time and scrap. What does an hour of standstill cost your company, and what can you claim after a long cut? Our article on compensation and the real cost of downtime does the sum.

Why do the lights flicker when a machine starts?

Flicker is a quick, repeated variation of the voltage, and it is caused by loads that switch on with a high current. Powerquality.nl names large motors started directly on the grid, spot welders and induction furnaces.

Flicker is measured with two figures: Pst over 10 minutes and Plt over 2 hours. You do not need them to spot it. When the lights in the office dip every time the compressor or the welder starts, you have flicker. Powerquality.nl notes that high flicker levels can cause headaches, tired eyes and loss of concentration.

The fix is usually on your side. A soft starter or a frequency drive lets the big motor start gently. A heavier connection or a shorter cable to the cabin also helps, but that is expensive and slow. A battery inverter can deliver the start-up current itself, so the grid never sees the peak. Lower start peaks also help against the Flemish capacity tariff, which bills your highest quarter-hour peak of the month. Our article on how the capacity tariff for businesses is calculated explains that part.

How do you find out whether voltage dips are behind your machine stops?

By measuring the voltage at your main switchboard with a power-quality analyser for one to two weeks. HyTEPS advises at least that period, so that weekends and busy days are both in the data.

An ordinary energy meter is not enough. It stores 10-minute averages, and a dip of 100 milliseconds disappears in such an average. HyTEPS recommends a class A analyser according to IEC 61000-4-30, which records every event with its depth and duration.

Put the measurement next to your list of stops. When the dips come from the grid, report them to your grid operator with the measured dates and times. Is the voltage too high for hours on end? Our article on inverters that trip on high voltage explains the complaint procedure at Fluvius.

Watch out

Stedin, a Dutch grid operator, explains that the grid rules separate troublesome dips from dips that customers can protect themselves against. No grid can avoid every short circuit, so part of the protection is always your job.

Which solutions keep your machines running through a voltage dip?

Start as close to the weak spot as you can: settings first, then the controls, and only then the whole line. The cheapest fix is often a setting, the most complete one is a system that feeds the loads permanently.

Solution What it protects Good for Limit
Settings on drives and controls (ride-through, automatic restart)One machineShort, shallow dipsAsk your machine builder; not every process may restart on its own
Soft starter or frequency drive on the big motorYour own installationDips and flicker you cause yourselfDoes nothing against grid dips
Small UPS in the control cabinetPLC, controls, networkKeeping the brain aliveThe motors still stop
Voltage-dip compensator (active voltage conditioner)A line or a hallDips, not full interruptionsNo back-up when the power is gone
Online UPS or battery system that feeds the loadsWhole circuits or the whole siteDips, micro-cuts and power cutsLargest investment; size it on your motors
GeneratorWhole site, for hoursLong power cutsStarts after seconds: too slow for a dip

The UPS type matters. According to Vertiv, an offline UPS leaves a break of about 6 to 8 milliseconds when it switches to battery. A line-interactive UPS leaves about 4 to 6. An online double-conversion UPS has no break at all, because the power runs through it all the time. Whether a few milliseconds is short enough depends on the equipment: ask your machine builder.

Our verdict

When the dips come from your own machines, fix them at the source with a soft starter or a drive. When only the controls reset, a small UPS in the control cabinet is the cheapest fix. A battery system that feeds the whole line earns its place when the stops are frequent and costly. It also does when you want back-up for real power cuts.

UPS or battery system: what protects a production line best?

A UPS protects a few devices for minutes, while a battery system can carry whole circuits for hours and does useful work on normal days. For IT and controls, a UPS is fine. For motors, drives and a full line, a battery system with the right inverter power is usually the better fit.

A battery system can work in two ways. In the first, the grid feeds your loads and the system takes over when the grid fails. Victron states that a MultiPlus-II takes over in less than 20 milliseconds, fast enough to keep computers running. In the second, the inverter feeds your critical loads all the time and the grid only charges the battery. Then your loads never see a dip, because they are not on the grid.

That second way is what we did in Gedinne. The grid delivered only 180 V, so the inverter makes a stable 3x400 V from the battery. A generator is coupled in for power cuts. It is the principle behind our semi off-grid system, in which the public grid acts as a generator.

Our article on dozens of small UPS units or one central battery weighs the two for servers and production lines. The article on which inverter a business actually needs explains the difference between solar, battery and UPS inverters.

Machines stopping on dips or micro-cuts? Tell us which ones, and we will tell you what it takes.

+32 494 36 37 91Contact usRequest a quote

What happens when you ask us to help with voltage dips on your site?

We start with what stops, and what it draws when it starts.

  1. Step 1: Analysis. We list the machines that stop, their start currents and the circuits they sit on. We measure your actual and peak consumption over a period. If the stops point to the grid, ask your electrician or a power-quality specialist for a class A measurement as well.
  2. Step 2: Technical design. We choose which circuits the battery system feeds, the inverter power for your motors and, where useful, a generator as second line.
  3. Step 3: Installation and commissioning.
  4. Step 4: Monitoring and support. You follow the consumption per phase and the state of charge in our monitoring software.

Our battery systems for businesses are built for back-up power and business continuity, from small SME installations to modular systems up to 1 MW.

Frequently asked questions

How long does a voltage dip last?

Between 10 milliseconds and one minute, according to EN 50160. HyTEPS notes that most dips last less than one second. That is why people rarely see them, but machines do.

Can a voltage dip damage equipment?

It can. Fortop, a Belgian automation company, names machine stops, crashes that need a reset and equipment damage among the effects. The most common cost is not damage but the stop and the restart.

Why does our generator not help against micro-cuts?

Because it only starts after the power has been gone for a few seconds. By then the micro-cut is over and your machines have already stopped. A generator is the answer for long cuts; our article on what to do in the first hour of a power cut covers those.

Do voltage dips also stop our solar panels?

Deep or long ones can. The Synergrid rule C10/11 makes solar inverters disconnect when the voltage leaves set limits. A battery system that forms its own local grid keeps them producing.

Should we ask the grid operator to fix it?

Report repeated dips with measured dates and times, especially when neighbours have the same problem. But count on protecting your own sensitive equipment as well: no grid operator can prevent every short circuit on its cables.

Want your line to keep running through the next dip?

Tell us which machines stop, how often and what a stop costs you. One of our engineers will tell you whether a setting, a small UPS or a battery system makes sense. You will also know what the same system does for your peaks and your solar power on the other days.

Contact usRequest a quote

Sources

  1. Janitza: voltage dips and interruptions
  2. HyTEPS: spanningsdips (knowledge base)
  3. Fortop: what are voltage dips?
  4. Stedin: spanningsdips
  5. ORES: no more electricity or gas (FAQ, micro-cuts)
  6. Powerquality.nl: flicker
  7. EN 50160 (overview)
  8. Vertiv: what are the different types of UPS systems?
  9. Victron Energy: MultiPlus-II
  10. Synergrid: technical prescription C10/11

About the author

YouPower. YouPower, based in Zele, has designed, sized and installed battery and off-grid energy systems for businesses, farms and homes since 2018. Victron Energy Certified Partner, own engineering office, open-source control and in-house battery recycling. More about YouPower